Fire resistance and types of construction (Type A, B and C)

For apartments and commercial buildings, the NCC sets how well the structure must resist fire, so the building stays standing and fire doesn't spread while people get out and firefighters work. It does this through three types of construction and fire-resistance levels for each part of the building.

Last checked: 13 November 2026. Based on NCC 2022 Volume One, Section C. For houses, see our fire separation guide. Check the edition and state variations that apply to your job.

Where the rules are

  • NCC Volume One, Section C, Fire resistance.
  • Part C2, Fire resistance and stability, including Table C2D2, Type of construction required.
  • Specification 5, Fire-resisting construction, which sets the FRLs for each building element.

Types of construction

Type A is the most fire-resistant, Type C the least, and Type B is in between. The type depends on the building's class and its rise in storeys (roughly, the number of storeys above ground, including storeys in the roof space):

Rise in storeysClass 2, 3 or 9Class 5, 6, 7 or 8
4 or moreAA
3AB
2BC
1CC

Residential and health-care buildings (2, 3, 9) need a higher type sooner, because people may be asleep or need help to get out.

Fire-resistance levels (FRLs)

An FRL is three numbers in minutes, written like 90/90/90:

  1. Structural adequacy: how long the element keeps carrying its load.
  2. Integrity: how long it stops flames and hot gases getting through.
  3. Insulation: how long it stops the far side getting too hot.

A dash means no requirement for that criterion, as in 60/–/– for a column. Specification 5 sets the FRL for each element (external walls, floors, columns, shafts, roofs) by type of construction, class and distance from a fire source such as a boundary.

Compartments and separation

Volume One also limits the size of fire compartments and requires separation between different classes in the same building, between sole-occupancy units, and around stairs, lift shafts and service shafts.

Penetrations

Every pipe, cable and duct through a fire-rated wall or floor is a weak point. Penetrations must be protected with tested systems (collars, wraps, sealants) installed the way they were tested. This is one of the most common defects in apartments, and one where electricians, plumbers and air-conditioning installers each leave their mark.

Combustible cladding

External walls of Type A and B buildings generally must be non-combustible, with limited exceptions. Combustible cladding on multi-storey buildings has led to major rectification programs in several states.

What inspectors should look for

  • Unsealed or poorly sealed penetrations in fire-rated walls and ceilings, often hidden above ceilings and in risers
  • Fire doors that don't close, are wedged open, or have been modified
  • Holes cut in fire-rated walls for new services
  • Combustible cladding on multi-storey buildings

Sources

  • NCC 2022 Volume One, Part C2 and Specification 5: ncc.abcb.gov.au

This guide is general information, not legal or fire engineering advice.