Fire separation near boundaries: walls, eaves and garages
When a house burns, the radiant heat can set fire to the house next door. The NCC stops that by requiring fire-resisting construction where houses sit close to a boundary or to each other. It catches out a lot of extensions, carports and granny flats.
Last checked: 13 November 2026. Based on NCC 2022 Housing Provisions Part 9.2. Check the edition and your state's variations (South Australia and WA have their own); this is a summary only.
Where the rules are
- NCC Volume Two, Part H3, Fire safety.
- Housing Provisions Part 9.2, Fire separation of external walls.
- Housing Provisions Part 9.3, Fire protection of separating walls and floors, for townhouses and terraces joined together.
When the rules apply
An external wall of a house, and any openings in it, must be fire-resisting if the wall is less than:
- 900 mm from a side or rear allotment boundary (not a boundary to a road or public space); or
- 1.8 m from another building on the same allotment, other than the house's own garage, shed or carport.
Distances are measured at right angles from the boundary or the other building.
What fire-resisting means here
A wall that has to be fire-resisting must achieve the required fire-resistance level (FRL), commonly 60/60/60 for houses, and run up to the underside of a non-combustible roof or non-combustible eaves lining. Windows and openings in that wall need protection or must be limited, with some concessions for small windows in non-habitable rooms.
Eaves, gutters and other encroachments
Things that stick out from the wall can encroach on the boundary zone, within limits:
- Non-combustible fascias, gutters and downpipes are allowed close to the boundary.
- Eaves are generally not allowed closer than 450 mm to a boundary, and need non-combustible lining where they are within the zone.
- Combustible items such as timber pergolas, unlined eaves and combustible roof lights are limited.
Garages and carports
A garage or carport (Class 10a) between a house and the boundary is a common trap. The Housing Provisions set out options: keep the garage 900 mm off the boundary, make its wall fire-resisting, or make the house wall fire-resisting. Where a carport roof is close to the house or boundary, the rules for roofed outdoor areas also apply.
Townhouses and terraces
Where houses are joined, the separating wall between them must be fire-resisting and continue to the underside of the roof covering, so fire cannot pass through the roof space.
What inspectors should look for
- Walls, eaves or pergolas very close to a side boundary, especially on newer extensions
- Timber or unlined eaves near the boundary
- Separating walls in townhouses that stop at the ceiling instead of the roof
- Penetrations through separating walls that have not been sealed
Sources
- NCC 2022 Volume Two, Part H3, and ABCB Housing Provisions Parts 9.2 and 9.3: ncc.abcb.gov.au
- HIA, "Preventing the spread of fire to Class 1a buildings"
This guide is general information, not legal or compliance advice.