Emergency lighting and exit signs: install, test, maintain
When the power fails in a fire, emergency lights and exit signs are what let people find their way out. The NCC says which buildings need them; Australian Standards say how they're designed, installed and tested. Six-monthly testing is a staple of commercial electrical work.
Last checked: 13 November 2026. Based on NCC 2022 Volume One, Part E4, and the way AS/NZS 2293 is used. State laws set maintenance and reporting. This summarises the Standard; it does not reproduce it.
Where the rules are
- NCC Volume One, Part E4, Visibility in an emergency, exit signs and warning systems.
- AS/NZS 2293.1, system design, installation and operation.
- AS/NZS 2293.2, routine service and maintenance.
- AS/NZS 2293.3, the emergency luminaires and exit signs themselves.
Which buildings need them
Part E4 requires emergency lighting in many Class 2 to 9 buildings, depending on the class, size and layout, including in fire-isolated stairs, passageways and ramps, and along paths to exits. Exit signs are required above or next to required exits and doors leading to them, and directional signs where the exit isn't obvious. Inside a sole-occupancy unit (an apartment), these rules generally don't apply.
The key numbers
- Emergency lighting must run for at least 90 minutes on battery after the mains fails.
- It must switch on automatically when the normal lighting fails.
- Exit signs must be visible whenever the building is occupied.
Testing
AS/NZS 2293.2 sets routine maintenance. In practice:
- Every six months: a discharge test. The mains supply is cut and every emergency light and exit sign must stay lit on battery for the full test duration.
- Every year: the six-monthly checks plus extra inspection and cleaning.
- A logbook must be kept on the premises, recording each test, any failures and the repairs.
Fittings that fail must be repaired or replaced, and replacement batteries need a recharge before the next discharge test.
Self-testing and monitored systems can run the tests automatically and report results, which cuts down on site visits.
Annual statements
Emergency lighting is usually one of the fire safety measures listed on a building's fire safety schedule, so its testing records support the annual fire safety statement. See our fire safety measures guide.
What inspectors and electricians should look for
- Exit signs not lit, or damaged
- Fittings with failed batteries (they won't light on test)
- No logbook on site, or gaps in the testing record
- Exit signs blocked by fit-outs, shelving or signage
- New partitions that leave an area without emergency lighting
Sources
- NCC 2022 Volume One, Part E4: ncc.abcb.gov.au
- City of Cockburn, guidelines for exit sign and emergency lighting inspection and maintenance
This guide is general information, not legal or electrical advice. AS/NZS 2293 is available from Standards Australia.