Smoke alarms in houses: what the NCC requires

Smoke alarms are cheap, and they save lives. The NCC sets out where they go, how they are powered and when they must be linked together in new houses, and each state has its own rules for existing homes, rentals and homes being sold.

This guide covers the NCC rules for new houses (Class 1), plus what electricians, builders and inspectors should check.

Last checked: 13 November 2026. Based on NCC 2022 Housing Provisions Part 9.5. State laws for existing homes and rentals differ; check yours.

Where the rules are

  • NCC Volume Two, Part H3, Fire safety.
  • Housing Provisions Part 9.5, Smoke alarms and evacuation lighting. NSW has its own version of this Part.

The three basics

In a new house, smoke alarms must:

  1. Comply with AS 3786, the Australian Standard for smoke alarms.
  2. Be powered from the mains where the building has mains power, usually with a battery backup.
  3. Be interconnected where there is more than one alarm, so when one sounds, they all sound. This applies within one dwelling; alarms in one townhouse do not have to link to the next one.

Where they go in a house (Class 1a)

The Housing Provisions set the locations with diagrams. In short, smoke alarms go:

  • On or near the ceiling in every storey that has bedrooms, between the bedrooms and the rest of the house. Where bedrooms are off a hallway, the alarm goes in the hallway.
  • Where bedrooms are in separate parts of the house, near each group of bedrooms.
  • On every other storey, even a storey with no bedrooms.

Small boarding houses and guest houses (Class 1b) need more: an alarm in every bedroom, in hallways serving bedrooms, and evacuation lighting.

Garages

Where a storey is a garage (Class 10a) that is part of the house, the NCC lets you use a heat alarm or other suitable alarm instead of a smoke alarm, because exhaust fumes cause false alarms. Smoke alarms that meet AS 3786 still have to be installed elsewhere in the house.

Placement tips

A smoke alarm in the wrong spot either never goes off or goes off all the time. AS 3786 covers the alarm itself, not where it goes, so follow the Housing Provisions and the manufacturer:

  • Keep alarms out of dead air spaces at the junction of the wall and ceiling, and away from the apex of a cathedral ceiling.
  • Keep them away from kitchens, bathrooms and air-conditioning outlets where steam and drafts cause false alarms.

Existing homes, rentals and sales

The NCC applies to new building work. Rules for existing homes come from state laws, and they vary:

  • Some states require interconnected, mains-powered alarms when a home is sold or rented.
  • Some require photoelectric alarms, or alarms in every bedroom.
  • Landlords usually have testing and replacement duties.

Check your state fire service or building regulator for the current rules.

What inspectors and electricians should check

  • Alarms in the right places on every storey
  • Interconnection works: test one and listen for the rest
  • Alarms within their replacement date (most are 10 years from manufacture)
  • Mains power in new homes, not battery-only units
  • Heat alarms, not smoke alarms, in attached garages

Sources

  • NCC 2022 Volume Two, Part H3, and ABCB Housing Provisions Part 9.5 (including the NSW variation): ncc.abcb.gov.au
  • WA Building and Energy, residential smoke alarm requirements

This guide is general information, not legal or compliance advice.