Backflow prevention: hazard ratings, devices and annual testing
Backflow is when water flows the wrong way: out of a building, a garden hose, a tank or a machine and back into the drinking water supply. It can carry fertiliser, chemicals, sewage or worse. The Plumbing Code of Australia requires protection against it, and the level of protection depends on the hazard.
Last checked: 13 November 2026. Based on the Plumbing Code of Australia and the way AS/NZS 3500.1 is called up. Water utilities and councils run their own backflow programs and registers. Check with yours.
Where the rules are
- NCC Volume Three (Plumbing Code of Australia), the cross-connection control provisions in Section B, Water services.
- AS/NZS 3500.1 Water services, which sets hazard ratings and the device needed for each.
- AS/NZS 2845 for the devices themselves.
- Local water utility and council backflow policies, which often set registration and testing requirements.
Hazard ratings
AS/NZS 3500.1 rates each cross-connection as one of three hazards:
| Hazard | What it means | Typical examples |
|---|---|---|
| High | Could cause death | Chemical dosing, hospitals, mortuaries, some industrial processes |
| Medium | Could endanger health | Many commercial premises, irrigation systems with fertiliser injection |
| Low | A nuisance, but not a danger to health | Most houses |
Where the hazard is unknown on commercial or industrial sites, councils commonly default to high.
Protection types
- Individual protection: at a single fixture or appliance.
- Zone protection: for a part of a building or a group of fixtures.
- Containment protection: at the property boundary, protecting the public supply from the whole site.
Devices
- Low hazard: non-testable devices such as dual check valves.
- Medium hazard: testable devices such as a double check valve.
- High hazard: testable devices such as a reduced pressure zone device (RPZD), or a registered air gap or break tank.
Testing
Testable devices must be commissioned when installed and tested at least every 12 months by a plumber with backflow accreditation. Results usually go to the water utility or council, which keeps a register. Owners are typically responsible for organising and paying for the testing.
Houses
Most houses are low hazard, and new homes usually have a dual check valve at the water meter. Things that can raise the hazard at home include a rainwater tank connected to the house, a bore, a pool or spa top-up, an irrigation system with fertiliser injection, or a non-compliant bidet seat. See our rainwater tank guide.
What inspectors should look for
- Garden hoses left in pools or buckets of chemicals
- Rainwater tanks connected to mains water without the required protection or air gap
- Testable devices with missing or out-of-date test tags on commercial sites
Sources
- AS/NZS 3500.1 hazard ratings as summarised in local water utility policies: MidCoast Council, Central Coast Council, Hunter Water, Barwon Water
- Building and Plumbing Commission Victoria, backflow information
This guide is general information, not legal or plumbing advice. AS/NZS 3500.1 is available from Standards Australia.